Hi-Output W-2.4-8.2 Wall VAD c/w 103dB(A) Sounder (shallow base)

Order code: BF433A/CX/SR Category:
  • Third-party certified to EN54-3 (Sounders), EN54-23 (VADs) and 17 (Isolators) by the LPCB.
  • Provides ‘W-2.4-8.2’ light distribution when wall mounted (min 0.4 lux over a 2.4m x8.2m cuboid area).
  • Impressive 103dB(A) sound output @ 1m.
  • Onboard short-circuit loop isolator.
  • 550µA quiescent current.
  • 14.5mA alarm current @24V DC (VAD lit, sounder on max).
  • Group addressing facility allows multiple devices to be operated simultaneously.
  • 7 selectable volume levels and up to 15 selectable tone pairs.
  • IP21C (Type A) rated.

     

Documentation
C-TEC’s VAD Guide – DML05382001.72 MB Download
XP95/Discovery Hi-Output Sounder VAD Instructions – DFU43000001.36 MB Download
XP95/Discovery Hi-Output Sounders Polar Diagram – DFU4300007491.62 KB Download
Approval Certificates
LPCB Third Party Approval Certificate – CAST, Hush-Pro & XP95/Discovery Sounder/VADs to EN54-3/23/17562.78 KB Download
EU CPR Certificate of Conformity – BF433A/CX/SR Hi-Output Sounder VAD Shallow (CoC)189.72 KB Download
EU Declaration of Conformity – XP95/Discovery Hi-Output Sounder VADs (DoC)164.00 KB Download
EU Declaration of Performance – XP95/Discovery Hi-Output Sounder VADs (DoP)190.66 KB Download
UKCA CPR Certificate of Conformity – BF433A/CX/SR Hi-Output Sounder VAD Shallow (CoC)194.86 KB Download
UKCA Declaration of Conformity – XP95/Discovery Hi-Output Sounder VADs (DoC)164.31 KB Download
UKCA Declaration of Performance – XP95/Discovery Hi-Output Sounder VADs (DoP)333.54 KB Download
BIM/CAD Drawings

BIM Drawing (REVIT)

This file will be uploaded to our website shortly.
Should you need an urgent copy please contact our
marketing team at marketing@c-tec.co.uk

Back to links

Back to links

CAD Drawing (DWG)

This file will be uploaded to our website shortly.
Should you need an urgent copy please contact our
marketing team at marketing@c-tec.co.uk

Back to links

Back to links

VAD coverage (with multiplication factors applied)

VAD coverage depends on factors such as ambient light and viewing angle (direct or indirect). The table below summarises how the coverage of the BF433A/CX/SR increases or decreases based on these factors. To use the table, calculate the lux level of the area requiring coverage, determine whether the viewing angle will be direct or indirect then read off the coverage in the relevant column. For further information refer to our VAD System Design Guide, downloadable from the Documentation tab below.

Lux level in area requiring coverageW-2.4-8.2 Wall Mounted Direct ViewingW-2.4-8.2 Wall Mounted Indirect ViewingW-4-4 Wall Mounted Direct ViewingW-4-4 Wall Mounted Indirect Viewing
000-101 lux12.5m H x 42.6m W4.3m H x 14.8m W20.8m H x 20.8m W7.2m H x 7.2m W
101-200 lux10.6m H x 36.1m H4.1m H x 13.9m W17.6m H x 17.6m W6.8m H x 6.8m W
201-300 lux7.7m H x 26.2m W3.4m H x 11.5m W12.8m H x 12.8m W5.6m H x 5.6m W
301-400 lux5.5m H x 18.9m W2.9m H x 9.8m W9.2m H x 9.2m W4.8m H x 4.8m W
401-500 lux4.3m H x 14.8m W2.4m H x 8.2m W7.2m H x 7.2m W4.0m H x 4.0m W
501-600 lux3.1m H x 10.7m W2.1m H x 7.4m W5.2m H x 5.2m W3.6m H x 3.6m W
601-700 lux2.4m H x 8.2m Wnot applicable4.0m H x 4.0m W2.8m H x 2.8m W
701-800 luxnot applicablenot applicable2.8m H x 2.8m Wnot applicable