C-3-8 Addressable Base VAD c/w 96dB(A) Sounder

Order code: BF456A/CX/W Category:
  • Third-party certified to EN54-3 (Sounders), EN54-23 (VADs) and 17 (Isolators) by the LPCB.
  • Provides ‘C-3-8’ light distribution (min 0.4 lux over a 3 x 8m cylindrical area).
  • Supplied with a BF431QCP quick connect plate and detector spur wires.
  • Impressive 96dB(A) sound output @ 1m.
  • Onboard short-circuit loop isolator.
  • 550µA quiescent current.
  • 14mA alarm current @24V DC (VAD lit, sounder on max).
  • Group addressing facility allows multiple devices to be operated simultaneously.
  • 7 selectable volume levels and up to 15 selectable tone pairs.
  • Optional BF330CTLIDW white or BF330CTLIDR red cap available for stand-alone use.
  • IP21C rated.

     

Documentation
XP95/Discovery Base Sounder VAD Instructions – DFU4310000 341.32 KB Download
C-TEC’s VAD Guide – DML0538200 1.72 MB Download
XP95/Discovery Base Sounders Polar Diagram – DFU4310007 261.31 KB Download
BF431QCP Quick Connect Plate Instructions – DFU4310020 364.29 KB Download
Approval Certificates
LPCB Third Party Approval Certificate – CAST, Hush-Pro & XP95/Discovery Sounder/VADs to EN54-3/23/17 562.78 KB Download
EU CPR Certificate of Conformity – BF456A/CX/W XP95/Discovery Base VAD c/w 96dB(A) Sounder (CoC) 195.33 KB Download
EU Declaration of Conformity – XP95/Discovery Base Sounder VADs (DoC) 162.33 KB Download
EU Declaration of Performance – XP95/Discovery Base Sounder VADs (DoP) 108.72 KB Download
UKCA CPR Certificate of Conformity – BF456A/CX/W XP95/Discovery Base VAD c/w 96dB(A) Sounder (CoC) 194.37 KB Download
UKCA Declaration of Conformity – XP95/Discovery Base Sounder VADs (DoC) 161.94 KB Download
UKCA Declaration of Performance – XP95/Discovery Base Sounder VADs (DoP) 331.79 KB Download
BIM/CAD Drawings

BIM Drawing (REVIT)

This file will be uploaded to our website shortly.
Should you need an urgent copy please contact our
marketing team at marketing@c-tec.co.uk

Back to links

Back to links

CAD Drawing (DWG)

This file will be uploaded to our website shortly.
Should you need an urgent copy please contact our
marketing team at marketing@c-tec.co.uk

Back to links

Back to links

VAD coverage (with multiplication factors applied)

VAD coverage depends on factors such as ambient light and viewing angle (direct or indirect). The table below summarises how the coverage of the BF456A/CX/W increases or decreases based on these factors. To use the table, calculate the lux level of the area requiring coverage, determine whether the viewing angle will be direct or indirect then read off the coverage in the relevant column. For further information refer to our VAD System Design Guide, downloadable from the Documentation tab below.

Lux level in area requiring coverage Ceiling Mounted Direct Viewing Ceiling Mounted Indirect Viewing
000-101 lux 8.3m H x 22.4m W 3.9m H x 10.4m W
101-200 lux 7.2m H x 19.2m H 3.6m H x 9.6m W
201-300 lux 5.7m H x 15.2m W 3.0m H x 8.0m W
301-400 lux 4.2m H x 11.2m W 2.4m H x 6.4m W
401-500 lux 3.3m H x 8.8m W 1.8m H x 4.8m W
501-600 lux 2.7m H x 7.2m W 1.5m H x 4.0m W
601-700 lux 2.1m H x 5.6m W not applicable
701-800 lux 1.5m H x 4.0m W not applicable