Compact W-3-3.1 Wall VAD

Order code: BF458A/CX/SR Category:
  • Third-party certified to EN54-23 (VADs) and 17 (Isolators) by Intertek.
  • Provides ‘W-3-3.1’ light distribution when wall mounted (min 0.4 lux over a 3 x 8m cylindrical area).
  • Can also provide ‘C-3-8’ light distribution when ceiling mounted (min. 0.4 lux over a 2.4 x 3.5m cuboid area).
  • Onboard short-circuit loop isolator.
  • 550µA quiescent current.
  • 10mA alarm current @24V DC.
  • Group addressing facility allows multiple devices to be operated simultaneously.
  • IP21C rated.

     

Documentation
C-TEC’s VAD Guide – DML0538200 1.72 MB Download
XP95/Discovery Compact Sounder VAD Instructions – DFU4500000 278.55 KB Download
XP95/Discovery Compact Sounders Polar Diagram – DFU4500007 232.16 KB Download
Approval Certificates
Intertek Third Party Approval Certificate – XP95/Discovery Compact Sounder/VADs to EN54-3/23/17 189.22 KB Download
EU CPR Certificate of Conformity – XP95/Discovery Compact Sounder/VADs (CoC) 948.11 KB Download
EU Declaration of Conformity – XP95/Discovery Compact Sounder VADs (DoC) 163.82 KB Download
EU Declaration of Performance – XP95/Discovery Compact Sounder VADs (DoP) 109.14 KB Download
UKCA CPR Certificate of Conformity – XP95/Discovery Compact Sounder/VADs (CoC) 172.70 KB Download
UKCA Declaration of Conformity – XP95/Discovery Compact Sounder VADs (DoC) 165.82 KB Download
UKCA Declaration of Performance – XP95/Discovery Compact Sounder VADs (DoP) 364.52 KB Download
BIM/CAD Drawings

BIM Drawing (REVIT)

This file will be uploaded to our website shortly.
Should you need an urgent copy please contact our
marketing team at marketing@c-tec.co.uk

Back to links

Back to links

CAD Drawing (DWG)

This file will be uploaded to our website shortly.
Should you need an urgent copy please contact our
marketing team at marketing@c-tec.co.uk

Back to links

Back to links

VAD coverage (with multiplication factors applied)

VAD coverage depends on factors such as ambient light and viewing angle (direct or indirect). The table below summarises how the coverage of the BF458A/CX/SR increases or decreases based on these factors. To use the table, calculate the lux level of the area requiring coverage, determine whether the viewing angle will be direct or indirect then read off the coverage in the relevant column. For further information refer to our VAD System Design Guide, downloadable from the Documentation tab below.

Ceiling Mounted  Ceiling Mounted  Wall Mounted WallMounted
Lux level in area requiring coverage Direct Viewing Indirect Viewing Direct Viewing Indirect Viewing
000-101 lux 8.3m H x 22.4m W 3.9m H x 10.4m W 15.6m H x 16.12m W 5.4m H x 5.58m W
101-200 lux 7.2m H x 19.2m H 3.6m H x 9.6m W 13.2m H x 13.64m W 5.1m H x 5.27m W
201-300 lux 5.7m H x 15.2m W 3.0m H x 8.0m W 9.6m H x 9.92m W 4.2m H x 4.34m W
301-400 lux 4.2m H x 11.2m W 2.4m H x 6.4m W 6.9m H x 7.13m W 3.6m H x 3.72m W
401-500 lux 3.3m H x 8.8m W 1.8m H x 4.8m W 5.4m H x 5.58m W 3.0m H x 3.1m W
501-600 lux 2.7m H x 7.2m W 1.5m H x 4.0m W 3.9m H x 4.03m W 2.7m H x 2.79m W
601-700 lux 2.1m H x 5.6m W not applicable 3.0m H x 3.1m W not applicable
701-800 lux 1.5m H x 4.0m W not applicable not applicable not applicable