Apollo Discovery Ionisation Smoke Detector

Order code: 58000-500APO Category:
  • A high specification ionisation smoke detector.
  • Fully compatible with C-TEC’s XFP & ZFP XP95/Discovery Addressable Fire Panels.
  • User programmable to operate in one of five sensitivity modes (e.g. Mode 1 will give a higher senstivity to fire than Mode 5).
  • Uses a low activity radioactive foil to detect fires by irradiating the air in the smoke chambers and causing a current flow.
  • Ideal for a wide range of applications.
  • Remote test feature.
  • Red LED illuminates when the detector is in alarm.
  • Certified to EN54-7 by the LPCB.
  • Requires a 45681-210APO standard base or 45681-242APO low power relay base.
  • ‘Xpert’ card addressed for speedy installation.
Operating Modes

The modes of operation for this detector, selectable from the XFP or ZFP control panel, are:-

Mode Alarm Threshold y Value Minimum Time to Alarm (seconds)
1 0.45 5
2 0.45 30
3 0.70 5
4 0.70 30
5 1.0 5

Compensation rate complies with EN54-7.