CAST Input Output Module

  • A versatile input output module with volt free changeover contacts that can be used to trigger rollershutters, door locking mechanisms, gas shut-off valves, smoke vents and more.
  • LPCB certified to EN54-17 & 18 and Kiwa Telefication & DBI certified to EN54-13.
  • EN54-13 & NTN 179L: 2021 certified by Belgian certification body BOSEC.
  • Also certified to the relevant parts of EN54 with Swedish certification body SBSC.
  • Can switch 1A@30V DC (or 0.3A@125V AC).
  • Incorporates the functions of a switch monitor, zone monitor and output unit.
  • Can be configured to monitor any combination of:-
    • Up to 20 conventional detectors & 10 MCPs
    • Any normally open switch with an EOL resistor fitted.
    • A simple normally open or closed switch (non-fault monitored).
  • Onboard short-circuit loop isolator.
  • 5.5mA typical alarm current (1.3mA typical quiescent current) @ 22-40V DC.
  • Indicators for Loop polling, input faults and relay status.
  • Mountable on a C-TEC NCP-26 surface box or a standard UK 25mm double gang back box (not supplied).

        

   

More Information

‘CAST’ is the world’s most-advanced ‘distributed intelligence’ fire alarm system protocol. Conceived, designed and realised by C-TEC, it involved the creation of a powerful proprietary communication protocol (C-TEC Addressable System Technology, CAST) and multiple control panels & field devices. Its key features include:-

• 255 devices per loop.
• Autonomous decision-making for faster response times.
• Multiple type codes.
• 40V loop drive voltage.
• Two ‘soft’ addressing options – automatic via the panel or manual via a powerful handheld programmer.
• Powerful multi-level addressing facilitates easy device addition and swapped device identification.
• Multiple functionality at a single address (integrated devices) via our CAST-PRO devices.
• Volumes, tones & detector modes can be changed at compatible panels.
• High-speed data transmission and robust data transfer.
• Intrinsically EN54-13 compliant.
• Geographical location of short and open circuit faults (a short circuit isolator is included as standard in every CAST field device).
• Replace device function.
• Future seamless integration with other CAST life safety systems reducing energy, servicing, installation and repair costs.
• Designed and manufactured in the UK.

Technical Specifications
Approvals/certifications

, , ,

Compatibility

Application/operation

Supply/operating voltage

Quiescent current

Activation current

Auxiliary relays

Auxiliary inputs

Indicators

Connections

Product dimensions (mm)

Construction & finish

IP Rating

Weight

Operating conditions/temperature

Documentation
XFP & ZFP CAST Addressable Fire Alarm System Brochure – DML0540100 5.16 MB Download
CA730 CAST I/O Unit Instructions – DFU7300000 290.39 KB Download
Approval Certificates
LPCB Third Party Approval Certificate – CAST & Hush-Pro I/O Modules etc to EN54-17/18 196.38 KB Download
KIWA Third Party Approval Certificate – XFP & ZFP CAST Fire Panels and CAST Devices to EN54-13 (Systems Approval) 130.87 KB Download
DBI Third Party Approval Certificate – ZFP CAST Fire Panels and CAST/CAST PRO Devices to EN54-13 (Systems Approval) 350.03 KB Download
BOSEC Third Party Approval Certificate – ZFP CAST Fire Panels and CAST Devices to EN54-13 & NTN 179-L (Systems Approval) 713.06 KB Download
SBSC Third Party Approval Certificate – ZFP CAST Fire Panels and CAST Devices to EN54 1.02 MB Download
EU CPR Certificate of Conformity – CAST CA730 I/O Module (CoC) 180.77 KB Download
EU Declaration of Conformity – CAST Input/Output Units (DoC) 74.24 KB Download
EU Declaration of Performance – CAST Input/Output Units (DoP) 172.37 KB Download
UKCA CPR Certificate of Conformity – CAST CA730 I/O Module (CoC) 192.52 KB Download
UKCA Declaration of Conformity – CAST Input/Output Units (DoC) 161.30 KB Download
UKCA Declaration of Performance – CAST Input/Output Units (DoP) 338.80 KB Download
BIM/CAD Drawings

CA730 (RFA)

Download


CA730 surface mounted BIM (RFA)

Download