CAST-PRO Smoke Detector c/w Voice Sounder & C-3-9.4 White VAD
- A CAST-PRO smoke detector c/w an 86db(A) voice sounder and a C-3-9.4 VAD.
- Certified to EN54-3, 7, 17 & 23 by Kiwa Telefication.
- Compatible with C-TEC’s ZFP and XFP CAST protocol addressable fire panels.
- MASC™ (Miniature Advanced Smoke Detection Chamber) and AFFIRM™ algorithms provide incredible tolerance to false alarms whilst enhancing the detection of real fire conditions.
- Drift compensation functionality.
- Onboard short circuit loop isolator.
- Includes two 8mm x 2mm ultra-bright red LED indicating strips.
- Multiple detection modes and different sensitivities for different times of the day.
- Six selectable voice messages with tones (2 evacuate, 1 alert, 1 all clear & 2 system test messages).
- 24.9mA max. alarm current (max vol, VAD on).
- 590uA typical quiescent current @ 40V DC.
- Compatible with C-TEC’s CA408 CAST base c/w integrated locking mechanism & ID tag.
![]()
More Information
‘CAST’ is the world’s most-advanced ‘distributed intelligence’ fire alarm system protocol. Conceived, designed and realised by C-TEC, it involved the creation of a powerful proprietary communication protocol (C-TEC Addressable System Technology, CAST) and multiple control panels & field devices. Its key features include:-
• 255 devices per loop.
• Autonomous decision-making for faster response times.
• Multiple type codes.
• 40V loop drive voltage.
• Two ‘soft’ addressing options – automatic via the panel or manual via a powerful handheld programmer.
• Powerful multi-level addressing facilitates easy device addition and swapped device identification.
• Multiple functionality at a single address (integrated devices) via our CAST-PRO devices.
• Volumes, tones & detector modes can be changed at compatible panels.
• High-speed data transmission and robust data transfer.
• Intrinsically EN54-13 compliant.
• Geographical location of short and open circuit faults (a short circuit isolator is included as standard in every CAST field device).
• Replace device function.
• Future seamless integration with other CAST life safety systems reducing energy, servicing, installation and repair costs.
• Designed and manufactured in the UK.
Technical Specifications
| Approvals/certifications | Certified to EN54-3, 7, 17 & 23 by Kiwa Telefication, CPR number 0063-CPR-252190034 |
|---|---|
| Compatibility | Compatible with C-TEC's XFP/ZFP CAST Protocol Addressable Fire Panels. |
| Type | |
| Sensitivity | 2 Detection Modes (normal or high sensitivity, default is normal) |
| Supply wiring | |
| Supply/operating voltage | |
| Quiescent current | |
| Alarm current (Imax at Vmin) | 24.9mA (max volume, VAD lit). |
| Alarm current (Iavg at Vmin) | 14.6mA (max volume, VAD lit). |
| Sound pressure level (LAFmax) at Vmax at 1m | 86dB(A). |
| VAD category & coverage | |
| Indicators | |
| Connections | |
| Product dimensions (mm) | 105mm diameter x 51mm deep (detector only); 105mm diameter x 68mm deep (detector in base). |
| IP Rating | |
| Weight | |
| Operating conditions/temperature | |
| Detection Type | Smoke only |
| VAD | White VAD |
| Sounder | Voice sounder |
| Housing | White |
| Notes | Requires a CA408 CAST base. CA408R relay base also available. |
Documentation
Approval Certificates
Voice Message Options
Messages – Pair One
Tone/Voice Message 1 (Primary)
Tone: Evacuate (550 Hz for 0.5 sec, 825 Hz for 0.5 sec);
Message: Attention please. Attention please. Fire has been reported in the building. Please leave immediately by the nearest exit. (repeated 2x)
Tone/Voice Message 2 (Secondary)
Tone: Alert (1 sec off, 825 Hz for 1 sec);
Message: This is a fire alert.This is a fire alert. Await further instructions. Await further instructions. (repeated 2x).
Messages – Pair Two
Tone/Voice Message 1 (Primary)
Tone: Evacuate (550 Hz for 0.5 sec, 825 Hz for 0.5;
Message: In the interests of safety please evacuate the building now. (repeated 3x).
Tone/Voice Message 2 (Secondary)
Tone: Alert (1 sec off, 825 Hz for 1 sec);
Message: All Clear. The emergency has been resolved. It is safe to resume normal activities. All Clear. (repeated 2x).
Messages – Pair Three
Tone/Voice Message 1 (Primary)
Tone: Evacuate (550 Hz for 0.5 sec, 825 Hz for 0.5 sec);
Message: This is a test of the fire alarm system. Please do not take any action. (repeated 2x).
Tone/Voice Message 2 (Secondary)
Tone: Alert (1 sec off, 825 Hz for 1 sec);
Message: The fire alarm test is now complete. (repeated 3x).
Detection Modes
The default detection mode for the CP416VV is Mode 2.
Full options are:-
Mode 1: High Sensitivity Smoke (0.1dB/m; 2.3%) – no heat.
Mode 2: Normal Sensitivity Smoke (0.24dB/m; 5.4%) – no heat.