CAST-PRO CO Fire + Smoke + Heat Multisensor

Order code: CP411 Category:
  • A programmable CAST-PRO CO fire + smoke + heat multisensor fire detector.
  • Certified to EN54-5, 7, 17, 29 & 31.
  • Compatible with C-TEC’s ZFP touchscreen-controlled CAST protocol addressable fire panel.
  • MASC™ (Miniature Advanced Smoke Detection Chamber) and AFFIRM™ algorithms provide incredible tolerance to false alarms whilst enhancing the detection of real fire conditions.
  • Drift compensation functionality.
  • Onboard short circuit loop isolator.
  • Includes two 8mm x 2mm ultra-bright red LED indicating strips.
  • Multiple detection modes and different sensitivities for different times of the day.
  • <1mA alarm current (max vol, VAD on).
  • 630uA typical quiescent current @ 40V DC.
  • Compatible with C-TEC’s CA408 CAST base c/w integrated locking mechanism & ID tag.

      

Documentation
CAST-PRO Brochure – DML0551600 92.00 KB Download
CAST PRO Device Instructions – DFU4110010 260.78 KB Download
CAST PRO Polar Diagrams – DFU4110010 280.79 KB Download
Approval Certificates
EU Declaration of Performance – CAST-PRO Fire Detectors (DoP) 180.20 KB Download
Detection Modes

The default detection mode for the CP411 is Mode 10. This is Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A2 heat + CO to EN54-31 (with additional CO detection to EN54-26, EN54-30 and EN50291-Mimic*).

Full options are:-
Mode 1: High Sensitivity Smoke (0.1dB/m; 2.3%) – no heat; no CO.
Mode 2: Normal Sensitivity Smoke (0.24dB/m; 5.4%) – no heat; no CO.
Mode 3: Heat Only A1R – no smoke; no CO.
Mode 4: Heat Only A2 – no smoke; no CO.
Mode 5: Heat Only B – no smoke; no CO.
Mode 6: High Sensitivity Smoke (0.1dB/m; 2.3%) + A1R heat – no CO.
Mode 7: Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A1R heat; no CO.
Mode 8: Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A2 heat; no CO.
Mode 9: High Sensitivity Smoke (0.1dB/m; 2.3%) + A1R heat + CO to EN54-31 NT*
Mode 10: Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A2 heat + CO to EN54-31 NT*
Mode 11: Low Sensitivity Smoke (2.5dB/m; 43.8%), no heat + CO to EN54-31 MT**
Mode 12: Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A2 heat + CO to EN54-31 NT***

* In addition to detecting CO to EN54-31, modes 9 and 10 although not certified to them also detect CO to EN 54-26, EN 54-30 and EN 50291(Mimic).
** In addition to detecting CO to EN54-31, mode 11 although not certified to it also detects CO to EN 50291(Mimic).
*** In addition to detecting CO to EN54-31, mode 12 although not certified to them also detects CO to EN 54-26, EN 54-30, CO Toxicity and EN 50291(Mimic).

Video