CAST-PRO CO Fire + Smoke + Heat Multisensor c/w Tone Sounder
- Multiple functionality in a single device – CO fire, smoke & heat multisensor fire detection plus a 92db(A) tone Alarm sounder – detects real fires quickly, reduces false alarms effectively and indicates true alarm conditions decisively.
- Certified to EN54-3, 5, 7, 13, 17, 29 & 31 by Kiwa Telefication.
- EN54-13 & NTN 179L: 2021 certified by Belgian certification body BOSEC.
- Compatible with C-TEC’s ZFP and XFP CAST protocol addressable fire panels.
- MASC™ (Miniature Advanced Smoke Detection Chamber) and AFFIRM™ algorithms provide incredible tolerance to false alarms whilst enhancing the detection of real fire conditions.
- Drift compensation functionality.
- Onboard short circuit loop isolator.
- Includes two 8mm x 2mm ultra-bright red LED indicating strips.
- Multiple detection modes and different sensitivities for different times of the day.
- 5.4mA max. alarm current (max volume).
- 630uA typical quiescent current @ 40V DC.
- Compatible with C-TEC’s CA408 CAST base c/w integrated locking mechanism & ID tag.
![]()
More Information
‘CAST’ is the world’s most-advanced ‘distributed intelligence’ fire alarm system protocol. Conceived, designed and realised by C-TEC, it involved the creation of a powerful proprietary communication protocol (C-TEC Addressable System Technology, CAST) and multiple control panels & field devices. Its key features include:-
• 255 devices per loop.
• Autonomous decision-making for faster response times.
• Multiple type codes.
• 40V loop drive voltage.
• Two ‘soft’ addressing options – automatic via the panel or manual via a powerful handheld programmer.
• Powerful multi-level addressing facilitates easy device addition and swapped device identification.
• Multiple functionality at a single address (integrated devices) via our CAST-PRO devices.
• Volumes, tones & detector modes can be changed at compatible panels.
• High-speed data transmission and robust data transfer.
• Intrinsically EN54-13 compliant.
• Geographical location of short and open circuit faults (a short circuit isolator is included as standard in every CAST field device).
• Replace device function.
• Future seamless integration with other CAST life safety systems reducing energy, servicing, installation and repair costs.
• Designed and manufactured in the UK.
Technical Specifications
| Approvals/certifications | Certified to EN54-13 by Kiwa Telefication, Certified to EN54-13 & NTN 179-L:2021 by BOSEC, Certified to EN54-3, 5, 7, 17, 29 & 31 by Kiwa Telefication, CPR number 0063-CPR-242190012 |
|---|---|
| Compatibility | Compatible with C-TEC's XFP/ZFP CAST Protocol Addressable Fire Panels. |
| Type | |
| Sensitivity | |
| Supply wiring | |
| Supply/operating voltage | |
| Quiescent current | |
| Alarm current (Imax at Vmin) | 5.4mA (max volume). |
| Alarm current (Iavg at Vmin) | 5.0mA (max volume). |
| Sound pressure level (LAFmax) at Vmax at 1m | 92dB(A). |
| VAD category & coverage | |
| Indicators | |
| Connections | |
| Product dimensions (mm) | 105mm diameter x 48mm deep (detector only); 105mm diameter x 65mm deep (detector in base). |
| IP Rating | |
| Weight | |
| Operating conditions/temperature | |
| Notes | Requires a CA408 CAST base. CA408R relay base also available. |
Documentation
Approval Certificates
| KIWA Approval & EU CPR Certificates of Conformity – CAST-PRO range to EN54-3/5/7/17/23/29/31 (zip folder) | 300.83 KB | Download |
| KIWA Third Party Approval Certificate – XFP & ZFP CAST Fire Panels and CAST Devices to EN54-13 (Systems Approval) | 130.87 KB | Download |
| BOSEC Third Party Approval Certificate – ZFP CAST Fire Panels and CAST Devices to EN54-13 & NTN 179-L (Systems Approval) | 713.06 KB | Download |
| EU Declaration of Conformity – CAST-PRO CP411 Range of Detectors (DoC) | 179.86 KB | Download |
| EU Declaration of Performance – CAST-PRO Fire Detectors & Sounders (DoP) | 175.35 KB | Download |
Tone List
Here is a list of the 32 tone options available on this product. Note that different tones can be assigned to different functions in our ZFP programming software, e.g. Tone 1 could be set as the Primary tone and Tone 7 could be set as the Secondary tone. (Note, Tone 0 = Sounder OFF).
1. C-TEC Evacuation Tone (UK)
Tone: 535Hz for 0.5s, 800Hz for 0.5s
2. Alert (ALL)
Tone: 825Hz, 1s on, 1s off
3. C-TEC Fast Warble (UK)
Tone: 800Hz for 0.25s, 645Hz for 0.25s
4. Medium Sweep (UK)
Tone: 800 – 970Hz at 1Hz
5. Dutch Slow Whoop (sweep) (NL)
Tone: 500-1200Hz for 3.5s, 0.5s off
6. DIN Tone (DE)
Tone: 1200Hz – 500Hz for 1s
7. Swedish Alternating Tone (SWE)
Tone: 660Hz, 150ms on, 150ms off
8. Swedish all clear (SWE)
Tone: 660Hz constant on
9. Swedish Local Warning (SWE)
Tone: 660Hz, 1.8s on, 1.8s off
10. Swedish Pre-mess (SWE)
Tone: 660Hz, 6.5s on, 13s off, 20s period
11. Swedish Turn Out (SWE)
Tone: 554Hz for 1s, 440Hz for 1s
12. Swedish tone (SWE)
Tone: 660Hz 0.5s on, 0.5s off
13. Evacuation Tone (Apollo Comparable) (UK)
Tone: 550Hz for 0.5s, 825Hz for 0.5s
14. Alternating (Hochiki/Fulleon Comparable) (UK)
Tone: 925Hz for 0.25s, 626Hz for 0.25s
15. French Fire Tone (FR)
Tone: 554Hz for 100ms/440Hz for 380ms to 420ms
16. Australian Alert Tone AS1670 (ISO7731) (AUS)
Tone: 420Hz 0.625s on/off
17. Australian Evacuation Tone AS1670 (AUS)
Tone: 500 – 1200Hz, 0.5s/0.5s off x 3/1.5s off
18. Aus (fast rise sweep) (AUS)
Tone: 3x(500-1200Hz for 0.5s), 0.25s off
19. NZ (slow rise sweep) (NZ)
Tone: 500-1200Hz for 3.75s, 0.25s off
20. US Temporal LF (ISO 8201) (USA)
Tone: 3x(970Hz, 0.5s on, 0.5 off), 1s off
21. US Temporal HF (ISO 8201) (USA)
Tone: 3x(2850Hz, 0.5s on, 0.5 off), 1s off
22. Simulated Bell (USA/General)
Tone: n/a
23. Singapore Alert Tone (SG)
Tone: 1kHz, 2kHz 0.5s alternating
24. PFEER Alert Tone (ALL)
Tone: 950Hz, 0.25s on, 0.25Hz off
25. PFEER Alert Tone (ALL)
Tone: 970Hz, 1s on, 1s off
26. ISO 8201 (ALL)
Tone: 970Hz, 0.5s on/0.5s off x 3/1.5s off
27. ISO 8201 (ALL)
Tone: 2850Hz, 0.5s on/0.5s off x 3/1.5s off
28. Misc Tone 1 (ALL)
Tone: 925Hz continuous
29. Misc Tone 2 (ALL)
Tone: 975Hz continuous
30. Misc Tone 3 (ALL)
Tone: 2850Hz continuous
31. Fast Sweep (ALL)
Tone: 2.5-2.85kHz at 9Hz
Detection Modes
The default detection mode for the CP411T is Mode 10. This is Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A2 heat + CO to EN54-31 (with additional CO detection to EN54-26, EN54-30 and EN50291-Mimic*).
Full options are:-
Mode 1: High Sensitivity Smoke (0.1dB/m; 2.3%) – no heat; no CO.
Mode 2: Normal Sensitivity Smoke (0.24dB/m; 5.4%) – no heat; no CO.
Mode 3: Heat Only A1R – no smoke; no CO.
Mode 4: Heat Only A2 – no smoke; no CO.
Mode 5: Heat Only B – no smoke; no CO.
Mode 6: High Sensitivity Smoke (0.1dB/m; 2.3%) + A1R heat – no CO.
Mode 7: Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A1R heat; no CO.
Mode 8: Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A2 heat; no CO.
Mode 9: High Sensitivity Smoke (0.1dB/m; 2.3%) + A1R heat + CO to EN54-31 NT*
Mode 10: Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A2 heat + CO to EN54-31 NT*
Mode 11: Low Sensitivity Smoke (2.5dB/m; 43.8%), no heat + CO to EN54-31 MT**
Mode 12: Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A2 heat + CO to EN54-31 NT***
* In addition to detecting CO to EN54-31, modes 9 and 10 although not certified to them also detect CO to EN 54-26, EN 54-30 and EN 50291(Mimic).
** In addition to detecting CO to EN54-31, mode 11 although not certified to it also detects CO to EN 50291(Mimic).
*** In addition to detecting CO to EN54-31, mode 12 although not certified to them also detects CO to EN 54-26, EN 54-30, CO Toxicity and EN 50291(Mimic).