CAST-PRO CO Fire + Smoke + Heat Multisensor c/w Voice Sounder
- Multiple functionality in a single device – CO fire, smoke & heat multisensor fire detection plus an 86db(A) voice sounder – detects real fires quickly, reduces false alarms effectively and indicates true alarm conditions decisively.
- Certified to EN54-3, 5, 7, 13, 17, 29 & 31 by Kiwa Telefication.
- EN54-13 & NTN 179L: 2021 certified by Belgian certification body BOSEC.
- Compatible with C-TEC’s ZFP and XFP CAST protocol addressable fire panels.
- MASC™ (Miniature Advanced Smoke Detection Chamber) and AFFIRM™ algorithms provide incredible tolerance to false alarms whilst enhancing the detection of real fire conditions.
- Drift compensation functionality.
- Onboard short circuit loop isolator.
- Includes two 8mm x 2mm ultra-bright red LED indicating strips.
- Multiple detection modes and different sensitivities for different times of the day.
- Six selectable voice messages with tones (2 evacuate, 1 alert, 1 all clear & 2 system test messages).
- 17.1mA max. alarm current (max vol, VAD on).
- 630uA typical quiescent current @ 40V DC.
- Compatible with C-TEC’s CA408 CAST base c/w integrated locking mechanism & ID tag.
![]()
Technical Specifications
| Approvals/certifications | Certified to EN54-13 by Kiwa Telefication, Certified to EN54-13 & NTN 179-L:2021 by BOSEC, Certified to EN54-3, 5, 7, 17, 29 & 31 by Kiwa Telefication, CPR number 0063-CPR-242190012 |
|---|---|
| Compatibility | Compatible with C-TEC's XFP/ZFP CAST Protocol Addressable Fire Panels. |
| Type | |
| Sensitivity | |
| Supply wiring | |
| Supply/operating voltage | |
| Quiescent current | |
| Alarm current (Imax at Vmin) | 17.1mA (max volume). |
| Alarm current (Iavg at Vmin) | 9.1mA (max volume). |
| Sound pressure level (LAFmax) at Vmax at 1m | 86dB(A). |
| VAD category & coverage | |
| Indicators | |
| Connections | |
| Product dimensions (mm) | 105mm diameter x 48mm deep (detector only); 105mm diameter x 65mm deep (detector in base). |
| IP Rating | |
| Weight | |
| Operating conditions/temperature | |
| Notes | Requires a CA408 CAST base. CA408R relay base also available. |
Documentation
Approval Certificates
| KIWA Approval & EU CPR Certificates of Conformity – CAST-PRO range to EN54-3/5/7/17/23/29/31 (zip folder) | 300.83 KB | Download |
| KIWA Third Party Approval Certificate – XFP & ZFP CAST Fire Panels and CAST Devices to EN54-13 (Systems Approval) | 130.87 KB | Download |
| BOSEC Third Party Approval Certificate – ZFP CAST Fire Panels and CAST Devices to EN54-13 & NTN 179-L (Systems Approval) | 713.06 KB | Download |
| EU Declaration of Conformity – CAST-PRO CP411 Range of Detectors (DoC) | 179.86 KB | Download |
| EU Declaration of Performance – CAST-PRO Fire Detectors & Sounders (DoP) | 175.35 KB | Download |
Voice Message Options
Messages – Pair One
Tone/Voice Message 1 (Primary)
Tone: Alternating (925Hz for 0.25s, 626Hz for 0.25s);
Message: Attention please. Attention please. Fire has been reported in the building. Please leave immediately by the nearest exit. (repeated 2x)
Tone/Voice Message 2 (Secondary)
Tone: Alert (1 sec off, 825 Hz for 1 sec);
Message: This is a fire alert.This is a fire alert. Await further instructions. Await further instructions. (repeated 2x).
Messages – Pair Two
Tone/Voice Message 1 (Primary)
Tone: Alternating (925Hz for 0.25s, 626Hz for 0.25s);
Message: In the interests of safety please evacuate the building now. (repeated 3x).
Tone/Voice Message 2 (Secondary)
Tone: Alert (1 sec off, 825 Hz for 1 sec);
Message: All Clear. The emergency has been resolved. It is safe to resume normal activities. All Clear. (repeated 2x).
Messages – Pair Three
Tone/Voice Message 1 (Primary)
Tone: Alert (1 sec off, 825 Hz for 1 sec);
Message: This is a test of the fire alarm system. Please do not take any action. (repeated 2x).
Tone/Voice Message 2 (Secondary)
Tone: Alert (1 sec off, 825 Hz for 1 sec);
Message: The fire alarm test is now complete. (repeated 3x).
Detection Modes
The default detection mode for the CP411V is Mode 10. This is Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A2 heat + CO to EN54-31 (with additional CO detection to EN54-26, EN54-30 and EN50291-Mimic*).
Full options are:-
Mode 1: High Sensitivity Smoke (0.1dB/m; 2.3%) – no heat; no CO.
Mode 2: Normal Sensitivity Smoke (0.24dB/m; 5.4%) – no heat; no CO.
Mode 3: Heat Only A1R – no smoke; no CO.
Mode 4: Heat Only A2 – no smoke; no CO.
Mode 5: Heat Only B – no smoke; no CO.
Mode 6: High Sensitivity Smoke (0.1dB/m; 2.3%) + A1R heat – no CO.
Mode 7: Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A1R heat; no CO.
Mode 8: Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A2 heat; no CO.
Mode 9: High Sensitivity Smoke (0.1dB/m; 2.3%) + A1R heat + CO to EN54-31 NT*
Mode 10: Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A2 heat + CO to EN54-31 NT*
Mode 11: Low Sensitivity Smoke (2.5dB/m; 43.8%), no heat + CO to EN54-31 MT**
Mode 12: Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A2 heat + CO to EN54-31 NT***
* In addition to detecting CO to EN54-31, modes 9 and 10 although not certified to them also detect CO to EN 54-26, EN 54-30 and EN 50291(Mimic).
** In addition to detecting CO to EN54-31, mode 11 although not certified to it also detects CO to EN 50291(Mimic).
*** In addition to detecting CO to EN54-31, mode 12 although not certified to them also detects CO to EN 54-26, EN 54-30, CO Toxicity and EN 50291(Mimic).