CAST-PRO CO Fire + Smoke + Heat Multisensor c/w Voice Sounder & O-C-1.9-4 Red VAD

Order code: CP411VVR Category:
  • Multiple functionality in a single device – CO fire, smoke & heat multisensor fire detection plus an 86db(A) voice sounder and an O-C-1.9-4 red VAD – detects real fires quickly, reduces false alarms effectively and indicates true alarm conditions decisively.
  • Certified to EN54-3, 5, 7, 13, 17, 23, 29 & 31 by Kiwa Telefication.
  • EN54-13 & NTN 179L: 2021 certified by Belgian certification body BOSEC.
  • Compatible with C-TEC’s ZFP and XFP CAST protocol addressable fire panels.
  • MASC™ (Miniature Advanced Smoke Detection Chamber) and AFFIRM™ algorithms provide incredible tolerance to false alarms whilst enhancing the detection of real fire conditions.
  • Drift compensation functionality.
  • Onboard short circuit loop isolator.
  • Includes two 8mm x 2mm ultra-bright red LED indicating strips.
  • Multiple detection modes and different sensitivities for different times of the day.
  • Six selectable voice messages with tones (2 evacuate, 1 alert, 1 all clear & 2 system test messages).
  • 24.9mA max. alarm current (max vol, VAD on).
  • 630uA typical quiescent current @ 22-40V DC.
  • Compatible with C-TEC’s CA408 CAST base c/w integrated locking mechanism & ID tag.

       

More Information

‘CAST’ is the world’s most-advanced ‘distributed intelligence’ fire alarm system protocol. Conceived, designed and realised by C-TEC, it involved the creation of a powerful proprietary communication protocol (C-TEC Addressable System Technology, CAST) and multiple control panels & field devices. Its key features include:-

• 255 devices per loop.
• Autonomous decision-making for faster response times.
• Multiple type codes.
• 40V loop drive voltage.
• Two ‘soft’ addressing options – automatic via the panel or manual via a powerful handheld programmer.
• Powerful multi-level addressing facilitates easy device addition and swapped device identification.
• Multiple functionality at a single address (integrated devices) via our CAST-PRO devices.
• Volumes, tones & detector modes can be changed at compatible panels.
• High-speed data transmission and robust data transfer.
• Intrinsically EN54-13 compliant.
• Geographical location of short and open circuit faults (a short circuit isolator is included as standard in every CAST field device).
• Replace device function.
• Future seamless integration with other CAST life safety systems reducing energy, servicing, installation and repair costs.
• Designed and manufactured in the UK.

Documentation
CAST-PRO Brochure – DML0551600 92.00 KB Download
CAST PRO Device Instructions – DFU4110010 260.78 KB Download
CAST PRO Polar Diagrams – DFU4110010 280.79 KB Download
Approval Certificates
KIWA Approval & EU CPR Certificates of Conformity – CAST-PRO range to EN54-3/5/7/17/23/29/31 (zip folder) 300.83 KB Download
KIWA Third Party Approval Certificate – XFP & ZFP CAST Fire Panels and CAST Devices to EN54-13 (Systems Approval) 130.87 KB Download
BOSEC Third Party Approval Certificate – ZFP CAST Fire Panels and CAST Devices to EN54-13 & NTN 179-L (Systems Approval) 713.06 KB Download
EU Declaration of Conformity – CAST-PRO CP411 Range of Detectors (DoC) 179.86 KB Download
EU Declaration of Performance – CAST-PRO Fire Detectors, Sounders & VADs (DoP) 204.18 KB Download
Voice Message Options

Messages – Pair One

Tone/Voice Message 1 (Primary)

Tone: Alternating (925Hz for 0.25s, 626Hz for 0.25s);
Message: Attention please. Attention please. Fire has been reported in the building. Please leave immediately by the nearest exit. (repeated 2x)

Tone/Voice Message 2 (Secondary)

Tone: Alert (1 sec off, 825 Hz for 1 sec);
Message: This is a fire alert.This is a fire alert. Await further instructions. Await further instructions. (repeated 2x).

Messages – Pair Two

Tone/Voice Message 1 (Primary)

Tone: Alternating (925Hz for 0.25s, 626Hz for 0.25s);
Message: In the interests of safety please evacuate the building now. (repeated 3x).

Tone/Voice Message 2 (Secondary)

Tone: Alert (1 sec off, 825 Hz for 1 sec);
Message: All Clear. The emergency has been resolved. It is safe to resume normal activities. All Clear. (repeated 2x).

Messages – Pair Three

Tone/Voice Message 1 (Primary)

Tone: Alert (1 sec off, 825 Hz for 1 sec);
Message: This is a test of the fire alarm system. Please do not take any action. (repeated 2x).

Tone/Voice Message 2 (Secondary)

Tone: Alert (1 sec off, 825 Hz for 1 sec);
Message: The fire alarm test is now complete. (repeated 3x).

Detection Modes

The default detection mode for the CP411VVR is Mode 10. This is Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A2 heat + CO to EN54-31 (with additional CO detection to EN54-26, EN54-30 and EN50291-Mimic*).

Full options are:-
Mode 1: High Sensitivity Smoke (0.1dB/m; 2.3%) – no heat; no CO.
Mode 2: Normal Sensitivity Smoke (0.24dB/m; 5.4%) – no heat; no CO.
Mode 3: Heat Only A1R – no smoke; no CO.
Mode 4: Heat Only A2 – no smoke; no CO.
Mode 5: Heat Only B – no smoke; no CO.
Mode 6: High Sensitivity Smoke (0.1dB/m; 2.3%) + A1R heat – no CO.
Mode 7: Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A1R heat; no CO.
Mode 8: Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A2 heat; no CO.
Mode 9: High Sensitivity Smoke (0.1dB/m; 2.3%) + A1R heat + CO to EN54-31 NT*
Mode 10: Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A2 heat + CO to EN54-31 NT*
Mode 11: Low Sensitivity Smoke (2.5dB/m; 43.8%), no heat + CO to EN54-31 MT**
Mode 12: Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A2 heat + CO to EN54-31 NT***

* In addition to detecting CO to EN54-31, modes 9 and 10 although not certified to them also detect CO to EN 54-26, EN 54-30 and EN 50291(Mimic).
** In addition to detecting CO to EN54-31, mode 11 although not certified to it also detects CO to EN 50291(Mimic).
*** In addition to detecting CO to EN54-31, mode 12 although not certified to them also detects CO to EN 54-26, EN 54-30, CO Toxicity and EN 50291(Mimic).

Video