CAST-PRO Smoke + Heat Multisensor c/w Voice Sounder & O-C-1.9-4 Red VAD

Order code: CP414VVR Category:
  • Multiple functionality in a single device – smoke & heat multisensor fire detection plus an 86db(A) voice sounder and an O-C-1.9-4 red VAD – detects real fires quickly, reduces false alarms effectively and indicates true alarm conditions decisively.
  • Certified to EN54-3, 5, 7, 17, 23, & 29.
  • Compatible with C-TEC’s ZFP touchscreen-controlled CAST protocol addressable fire panel.
  • MASC™ (Miniature Advanced Smoke Detection Chamber) and AFFIRM™ algorithms provide incredible tolerance to false alarms whilst enhancing the detection of real fire conditions.
  • Drift compensation functionality.
  • Onboard short circuit loop isolator.
  • Includes two 8mm x 2mm ultra-bright red LED indicating strips.
  • Multiple detection modes and different sensitivities for different times of the day.
  • Six selectable voice messages with tones (2 evacuate, 1 alert, 1 all clear & 2 system test messages).
  • 24.9mA max. alarm current (max vol, VAD on).
  • 590uA typical quiescent current @ 40V DC.
  • Compatible with C-TEC’s CA408 CAST base c/w integrated locking mechanism & ID tag.

      

Documentation
CAST-PRO Brochure – DML0551600 92.00 KB Download
CAST PRO Device Instructions – DFU4110010 260.78 KB Download
CAST PRO Polar Diagrams – DFU4110010 280.79 KB Download
Approval Certificates
EU CPR Certificate of Conformity – CP414 range (heat/optical/tone/voice/VAD) 300.82 KB Download
EU Declaration of Performance – CAST-PRO Fire Detectors, Sounders & VADs (DoP) 204.18 KB Download
Voice Message Options

Messages – Pair One

Tone/Voice Message 1 (Primary)

Tone: Evacuate (550 Hz for 0.5 sec, 825 Hz for 0.5 sec);
Message: Attention please. Attention please. Fire has been reported in the building. Please leave immediately by the nearest exit. (repeated 2x)

Tone/Voice Message 2 (Secondary)

Tone: Alert (1 sec off, 825 Hz for 1 sec);
Message: This is a fire alert.This is a fire alert. Await further instructions. Await further instructions. (repeated 2x).

Messages – Pair Two

Tone/Voice Message 1 (Primary)

Tone: Evacuate (550 Hz for 0.5 sec, 825 Hz for 0.5;
Message: In the interests of safety please evacuate the building now. (repeated 3x).

Tone/Voice Message 2 (Secondary)

Tone: Alert (1 sec off, 825 Hz for 1 sec);
Message: All Clear. The emergency has been resolved. It is safe to resume normal activities. All Clear. (repeated 2x).

Messages – Pair Three

Tone/Voice Message 1 (Primary)

Tone: Evacuate (550 Hz for 0.5 sec, 825 Hz for 0.5 sec);
Message: This is a test of the fire alarm system. Please do not take any action. (repeated 2x).

Tone/Voice Message 2 (Secondary)

Tone: Alert (1 sec off, 825 Hz for 1 sec);
Message: The fire alarm test is now complete. (repeated 3x).

Detection Modes

The default detection mode for the CP414VVR is Mode 7. This is Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A1R heat.

Full options are:-
Mode 1: High Sensitivity Smoke (0.1dB/m; 2.3%) – no heat.
Mode 2: Normal Sensitivity Smoke (0.24dB/m; 5.4%) – no heat.
Mode 3: Heat Only A1R – no smoke.
Mode 4: Heat Only A2 – no smoke.
Mode 5: Heat Only B – no smoke.
Mode 6: High Sensitivity Smoke (0.1dB/m; 2.3%) + A1R heat.
Mode 7: Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A1R heat.
Mode 8: Normal Sensitivity Smoke (0.24dB/m; 5.4%) + A2 heat.

Video