CAST-PRO Smoke Detector c/w Tone Sounder & C-3-9.4 White VAD
- A CAST-PRO smoke detector c/w a 92db(A) tone Alarm sounder and a C-3-9.4 VAD.
- Certified to EN54-3, 7, 17 & 23 by Kiwa Telefication.
- Compatible with C-TEC’s ZFP and XFP CAST protocol addressable fire panels.
- MASC™ (Miniature Advanced Smoke Detection Chamber) and AFFIRM™ algorithms provide incredible tolerance to false alarms whilst enhancing the detection of real fire conditions.
- Drift compensation functionality.
- Onboard short circuit loop isolator.
- Includes two 8mm x 2mm ultra-bright red LED indicating strips.
- Multiple detection modes and different sensitivities for different times of the day.
- 13.2mA max. alarm current (max vol, VAD on).
- 590uA typical quiescent current @ 40V DC.
- Compatible with C-TEC’s CA408 CAST base c/w integrated locking mechanism & ID tag.
![]()
More Information
‘CAST’ is the world’s most-advanced ‘distributed intelligence’ fire alarm system protocol. Conceived, designed and realised by C-TEC, it involved the creation of a powerful proprietary communication protocol (C-TEC Addressable System Technology, CAST) and multiple control panels & field devices. Its key features include:-
• 255 devices per loop.
• Autonomous decision-making for faster response times.
• Multiple type codes.
• 40V loop drive voltage.
• Two ‘soft’ addressing options – automatic via the panel or manual via a powerful handheld programmer.
• Powerful multi-level addressing facilitates easy device addition and swapped device identification.
• Multiple functionality at a single address (integrated devices) via our CAST-PRO devices.
• Volumes, tones & detector modes can be changed at compatible panels.
• High-speed data transmission and robust data transfer.
• Intrinsically EN54-13 compliant.
• Geographical location of short and open circuit faults (a short circuit isolator is included as standard in every CAST field device).
• Replace device function.
• Future seamless integration with other CAST life safety systems reducing energy, servicing, installation and repair costs.
• Designed and manufactured in the UK.
Technical Specifications
| Approvals/certifications | Certified to EN54-3, 7, 17 & 23 by Kiwa Telefication, CPR number 0063-CPR-252190034 |
|---|---|
| Compatibility | Compatible with C-TEC's XFP/ZFP CAST Protocol Addressable Fire Panels. |
| Type | |
| Sensitivity | 2 Detection Modes (normal or high sensitivity, default is normal) |
| Supply wiring | |
| Supply/operating voltage | |
| Quiescent current | |
| Alarm current (Imax at Vmin) | 13.2mA (max volume, VAD lit). |
| Alarm current (Iavg at Vmin) | 10.8mA (max volume, VAD lit). |
| Sound pressure level (LAFmax) at Vmax at 1m | 92dB(A). |
| VAD category & coverage | |
| Indicators | |
| Connections | |
| Product dimensions (mm) | 105mm diameter x 51mm deep (detector only); 105mm diameter x 68mm deep (detector in base). |
| IP Rating | |
| Weight | |
| Operating conditions/temperature | |
| Detection Type | Smoke only |
| VAD | White VAD |
| Sounder | Tone sounder |
| Housing | White |
| Notes | Requires a CA408 CAST base. CA408R relay base also available. |
Documentation
Approval Certificates
Tone List
Here is a list of the 32 tone options available on this product. Note that different tones can be assigned to different functions in our ZFP programming software, e.g. Tone 1 could be set as the Primary tone and Tone 7 could be set as the Secondary tone. (Note, Tone 0 = Sounder OFF).
1. C-TEC Evacuation Tone (UK)
Tone: 535Hz for 0.5s, 800Hz for 0.5s
2. Alert (ALL)
Tone: 825Hz, 1s on, 1s off
3. C-TEC Fast Warble (UK)
Tone: 800Hz for 0.25s, 645Hz for 0.25s
4. Medium Sweep (UK)
Tone: 800 – 970Hz at 1Hz
5. Dutch Slow Whoop (sweep) (NL)
Tone: 500-1200Hz for 3.5s, 0.5s off
6. DIN Tone (DE)
Tone: 1200Hz – 500Hz for 1s
7. Swedish Alternating Tone (SWE)
Tone: 660Hz, 150ms on, 150ms off
8. Swedish all clear (SWE)
Tone: 660Hz constant on
9. Swedish Local Warning (SWE)
Tone: 660Hz, 1.8s on, 1.8s off
10. Swedish Pre-mess (SWE)
Tone: 660Hz, 6.5s on, 13s off, 20s period
11. Swedish Turn Out (SWE)
Tone: 554Hz for 1s, 440Hz for 1s
12. Swedish tone (SWE)
Tone: 660Hz 0.5s on, 0.5s off
13. Evacuation Tone (Apollo Comparable) (UK)
Tone: 550Hz for 0.5s, 825Hz for 0.5s
14. Alternating (Hochiki/Fulleon Comparable) (UK)
Tone: 925Hz for 0.25s, 626Hz for 0.25s
15. French Fire Tone (FR)
Tone: 554Hz for 100ms/440Hz for 380ms to 420ms
16. Australian Alert Tone AS1670 (ISO7731) (AUS)
Tone: 420Hz 0.625s on/off
17. Australian Evacuation Tone AS1670 (AUS)
Tone: 500 – 1200Hz, 0.5s/0.5s off x 3/1.5s off
18. Aus (fast rise sweep) (AUS)
Tone: 3x(500-1200Hz for 0.5s), 0.25s off
19. NZ (slow rise sweep) (NZ)
Tone: 500-1200Hz for 3.75s, 0.25s off
20. US Temporal LF (ISO 8201) (USA)
Tone: 3x(970Hz, 0.5s on, 0.5 off), 1s off
21. US Temporal HF (ISO 8201) (USA)
Tone: 3x(2850Hz, 0.5s on, 0.5 off), 1s off
22. Simulated Bell (USA/General)
Tone: n/a
23. Singapore Alert Tone (SG)
Tone: 1kHz, 2kHz 0.5s alternating
24. PFEER Alert Tone (ALL)
Tone: 950Hz, 0.25s on, 0.25Hz off
25. PFEER Alert Tone (ALL)
Tone: 970Hz, 1s on, 1s off
26. ISO 8201 (ALL)
Tone: 970Hz, 0.5s on/0.5s off x 3/1.5s off
27. ISO 8201 (ALL)
Tone: 2850Hz, 0.5s on/0.5s off x 3/1.5s off
28. Misc Tone 1 (ALL)
Tone: 925Hz continuous
29. Misc Tone 2 (ALL)
Tone: 975Hz continuous
30. Misc Tone 3 (ALL)
Tone: 2850Hz continuous
31. Fast Sweep (ALL)
Tone: 2.5-2.85kHz at 9Hz
Detection Modes
The default detection mode for the CP416TV is Mode 2.
Full options are:-
Mode 1: High Sensitivity Smoke (0.1dB/m; 2.3%) – no heat.
Mode 2: Normal Sensitivity Smoke (0.24dB/m; 5.4%) – no heat.