CAST-PRO Smoke Detector c/w Tone Sounder & C-3-9.4 White VAD

Order code: CP416TV Category:
  • A CAST-PRO smoke detector c/w a 92db(A) tone Alarm sounder and a C-3-9.4 VAD.
  • Certified to EN54-3, 7, 17 & 23 by Kiwa Telefication.
  • Compatible with C-TEC’s ZFP and XFP CAST protocol addressable fire panels.
  • MASC™ (Miniature Advanced Smoke Detection Chamber) and AFFIRM™ algorithms provide incredible tolerance to false alarms whilst enhancing the detection of real fire conditions.
  • Drift compensation functionality.
  • Onboard short circuit loop isolator.
  • Includes two 8mm x 2mm ultra-bright red LED indicating strips.
  • Multiple detection modes and different sensitivities for different times of the day.
  • 13.2mA max. alarm current (max vol, VAD on).
  • 590uA typical quiescent current @ 40V DC.
  • Compatible with C-TEC’s CA408 CAST base c/w integrated locking mechanism & ID tag.

       

More Information

‘CAST’ is the world’s most-advanced ‘distributed intelligence’ fire alarm system protocol. Conceived, designed and realised by C-TEC, it involved the creation of a powerful proprietary communication protocol (C-TEC Addressable System Technology, CAST) and multiple control panels & field devices. Its key features include:-

• 255 devices per loop.
• Autonomous decision-making for faster response times.
• Multiple type codes.
• 40V loop drive voltage.
• Two ‘soft’ addressing options – automatic via the panel or manual via a powerful handheld programmer.
• Powerful multi-level addressing facilitates easy device addition and swapped device identification.
• Multiple functionality at a single address (integrated devices) via our CAST-PRO devices.
• Volumes, tones & detector modes can be changed at compatible panels.
• High-speed data transmission and robust data transfer.
• Intrinsically EN54-13 compliant.
• Geographical location of short and open circuit faults (a short circuit isolator is included as standard in every CAST field device).
• Replace device function.
• Future seamless integration with other CAST life safety systems reducing energy, servicing, installation and repair costs.
• Designed and manufactured in the UK.

Documentation
CAST-PRO Brochure – DML0551600 92.00 KB Download
CAST PRO Optical/Heat Range Instructions – DFU4110040 360.74 KB Download
CAST PRO Polar Diagrams – DFU4110050 280.79 KB Download
Approval Certificates
KIWA Approval & EU CPR Certificates of Conformity – CAST-PRO range to EN54-3/5/7/17/23/29/31 (zip folder) 300.83 KB Download
EU Declaration of Conformity – CAST-PRO CP416 Range of Detectors (DoC) 428.28 KB Download
Tone List

Here is a list of the 32 tone options available on this product. Note that different tones can be assigned to different functions in our ZFP programming software, e.g. Tone 1 could be set as the Primary tone and Tone 7 could be set as the Secondary tone. (Note, Tone 0 = Sounder OFF).

1. C-TEC Evacuation Tone (UK)

Tone: 535Hz for 0.5s, 800Hz for 0.5s

2. Alert (ALL)

Tone: 825Hz, 1s on, 1s off

3. C-TEC Fast Warble (UK)

Tone: 800Hz for 0.25s, 645Hz for 0.25s

4. Medium Sweep (UK)

Tone: 800 – 970Hz at 1Hz

5. Dutch Slow Whoop (sweep) (NL)

Tone: 500-1200Hz for 3.5s, 0.5s off

6. DIN Tone (DE)

Tone: 1200Hz – 500Hz for 1s

7. Swedish Alternating Tone (SWE)

Tone: 660Hz, 150ms on, 150ms off

8. Swedish all clear (SWE)

Tone: 660Hz constant on

9. Swedish Local Warning (SWE)

Tone: 660Hz, 1.8s on, 1.8s off

10. Swedish Pre-mess (SWE)

Tone: 660Hz, 6.5s on, 13s off, 20s period

11. Swedish Turn Out (SWE)

Tone: 554Hz for 1s, 440Hz for 1s

12. Swedish tone (SWE)

Tone: 660Hz 0.5s on, 0.5s off

13. Evacuation Tone (Apollo Comparable) (UK)

Tone: 550Hz for 0.5s, 825Hz for 0.5s

14. Alternating (Hochiki/Fulleon Comparable) (UK)

Tone: 925Hz for 0.25s, 626Hz for 0.25s

15. French Fire Tone (FR)

Tone: 554Hz for 100ms/440Hz for 380ms to 420ms

16. Australian Alert Tone AS1670 (ISO7731) (AUS)

Tone: 420Hz 0.625s on/off

17. Australian Evacuation Tone AS1670 (AUS)

Tone: 500 – 1200Hz, 0.5s/0.5s off x 3/1.5s off

18. Aus (fast rise sweep) (AUS)

Tone: 3x(500-1200Hz for 0.5s), 0.25s off

19. NZ (slow rise sweep) (NZ)

Tone: 500-1200Hz for 3.75s, 0.25s off

20. US Temporal LF (ISO 8201) (USA)

Tone: 3x(970Hz, 0.5s on, 0.5 off), 1s off

21. US Temporal HF (ISO 8201) (USA)

Tone: 3x(2850Hz, 0.5s on, 0.5 off), 1s off

22. Simulated Bell (USA/General)

Tone: n/a

23. Singapore Alert Tone (SG)

Tone: 1kHz, 2kHz 0.5s alternating

24. PFEER Alert Tone (ALL)

Tone: 950Hz, 0.25s on, 0.25Hz off

25. PFEER Alert Tone (ALL)

Tone: 970Hz, 1s on, 1s off

26. ISO 8201 (ALL)

Tone: 970Hz, 0.5s on/0.5s off x 3/1.5s off

27. ISO 8201 (ALL)

Tone: 2850Hz, 0.5s on/0.5s off x 3/1.5s off

28. Misc Tone 1 (ALL)

Tone: 925Hz continuous

29. Misc Tone 2 (ALL)

Tone: 975Hz continuous

30. Misc Tone 3 (ALL)

Tone: 2850Hz continuous

31. Fast Sweep (ALL)

Tone: 2.5-2.85kHz at 9Hz

Detection Modes

The default detection mode for the CP416TV is Mode 2.

Full options are:-
Mode 1: High Sensitivity Smoke (0.1dB/m; 2.3%) – no heat.
Mode 2: Normal Sensitivity Smoke (0.24dB/m; 5.4%) – no heat.

Video