ActiV Conventional Hi-Output 100dB(A) Wall Sounder (shallow base)
- Third-party certified to EN54-3 (Sounders).
- Impressive 100dB(A) sound output @ 1m.
- Includes 31 selectable primary tones and an optional secondary tone.
- Two volume levels (high and low)
- Alarm Current at 30Vdc = 5.5mA.
- Alarm Current at 18Vdc = 3.8mA.
- IP21C rated.
- Manufactured in the UK by C-TEC.
Technical Specifications
Approvals/certifications | |
---|---|
Protocol/compatibility | |
Application/operation | |
VAD category & coverage | |
Flash rate & colour | |
Supply/operating voltage | |
Nominal SPL (Sound Pressure Level) | |
Alarm current | |
Product dimensions (mm) | |
IP Rating | |
Weight | |
Operating conditions/temperature |
Documentation
Approval Certificates
LPCB Third Party Approval Certificate – ActiV Conventional Sounders to EN54-3 | 250.02 KB | Download |
VdS Third Party Approval Certificate – ActiV Hi-Output BF430C/CC Range to EN54-3 | 1.65 MB | Download |
EU CPR Certificate of Conformity – BF430C/CC/SR ActiV Hi-Output 100dB(A) Wall Sounder Shallow (CoC) | 188.38 KB | Download |
EU Declaration of Conformity – ActiV Hi-Output Sounder VADs (DoC) | 76.00 KB | Download |
EU Declaration of Performance – ActiV Hi-Output Sounder VADs (DoP) | 181.57 KB | Download |
UKCA CPR Certificate of Conformity – BF430C/CC/SR ActiV Hi-Output 100dB(A) Wall Sounder Shallow (CoC) | 195.04 KB | Download |
UKCA Declaration of Conformity – ActiV Hi-Output Sounder VADs (DoC) | 117.01 KB | Download |
UKCA Declaration of Performance – ActiV Hi-Output Sounder VADs (DoP) | 348.16 KB | Download |
Tone List
Here is a list of the 31 primary tone options available on this product (note that Tone 0 = sounder OFF).
Primary Tone List
1. C-TEC Evacuation Tone (UK)
Tone: 610Hz for 0.5s, 810Hz for 0.5s
2. Alert (ALL)
Tone: 825Hz, 1s on, 1s off
3. C-TEC Fast Warble (UK)
Tone: 810Hz for 0.25s, 610Hz for 0.25s
4. Medium Sweep (UK)
Tone: 800 – 970Hz at 1Hz
5. Dutch Slow Whoop (sweep) (NL)
Tone: 500-1200Hz for 3.5s, 0.5s off
6. DIN Tone (DE)
Tone: 1200Hz – 500Hz for 1s
7. Swedish Alternating Tone (SWE)
Tone: 660Hz, 150ms on, 150ms off
8. Swedish all clear (SWE)
Tone: 660Hz constant on
9. Swedish Local Warning (SWE)
Tone: 660Hz, 1.8s on, 1.8s off
10. Swedish Pre-mess (SWE)
Tone: 660Hz, 6.5s on, 13s off, 20s period
11. Swedish Turn Out (SWE)
Tone: 554Hz for 1s, 440Hz for 1s
12. Swedish tone (SWE)
Tone: 660Hz 0.5s on, 0.5s off
13. Evacuation Tone (Apollo Comparable) (UK)
Tone: 550Hz for 0.5s, 825Hz for 0.5s
14. Alternating (Hochiki/Fulleon Comparable) (UK)
Tone: 925Hz for 0.25s, 626Hz for 0.25s
15. French Fire Tone (FR)
Tone: 554Hz for 100ms/440Hz for 380ms to 420ms
16. Australian Alert Tone AS1670 (ISO7731) (AUS)
Tone: 420Hz 0.625s on/off
17. Australian Evacuation Tone AS1670 (AUS)
Tone: 500 – 1200Hz, 0.5s/0.5s off x 3/1.5s off
18. Aus (fast rise sweep) (AUS)
Tone: 3x(500-1200Hz for 0.5s), 0.25s off
19. NZ (slow rise sweep) (NZ)
Tone: 500-1200Hz for 3.75s, 0.25s off
20. US Temporal LF (ISO 8201) (USA)
Tone: 3x(970Hz, 0.5s on, 0.5 off), 1s off
21. US Temporal HF (ISO 8201) (USA)
Tone: 3x(2850Hz, 0.5s on, 0.5 off), 1s off
22. Simulated Bell (USA/General)
Tone: n/a
23. Singapore Alert Tone (SG)
Tone: 1kHz, 2kHz 0.5s alternating
24. PFEER Alert Tone (ALL)
Tone: 950Hz, 0.25s on, 0.25Hz off
25. PFEER Alert Tone (ALL)
Tone: 970Hz, 1s on, 1s off
26. ISO 8201 (ALL)
Tone: 970Hz, 0.5s on/0.5s off x 3/1.5s off
27. ISO 8201 (ALL)
Tone: 2850Hz, 0.5s on/0.5s off x 3/1.5s off
28. Misc Tone 1 (ALL)
Tone: 925Hz continuous
29. Misc Tone 2 (ALL)
Tone: 975Hz continuous
30. Misc Tone 3 (ALL)
Tone: 2850Hz continuous
31. Fast Sweep (ALL)
Tone: 2.5-2.85kHz at 9Hz
In addition to the above primary tone options, one optional secondary tone is available, see below. Please refer to the device’s wiring instructions for details on how to select this.
Optional Secondary Tone
Tone: 2.5-2.85kHz at 9Hz