Self testing 100dB Evacuation Alert sounder/visual alarm device, white
- Designed for use on a C-TEC CAST-powered EVAC-ALERT system.
- Provides audible and visual indication of an evacuation alert to help satisfy the requirements of the Equality Act.
- Impressive 100dBA sound output at 1m.
- Max. Alarm Current at 30Vdc = 21.7mA (Max. volume/0.5Hz flash).
- Typical Alarm Current at 30Vdc = 13.4mA (Max. volume/0.5Hz flash).
- Important: If using this device with a CA737 4-8 Way Flat Interface, the Interface must have a 1A CA737PSU fitted.
- IP21C rated.
- Designed to comply with EN54-3 and 23.
- Reliable hard-wired technology (for C-TEC’s position on using wireless devices as part of an evacuation alert system / system of last resort click here).
- Red version also available (order code BF433C/EA/SR).
Technical Specifications
| Compatibility | Designed for use with C-TEC's CAST-powered EVAC-ALERT evacuation alert system. |
|---|---|
| Alarm current | Max. @ 30Vdc = 21.7mA; Typ. @ 30Vdc = 13.4mA (Max. volume/0.5Hz flash). |
| Onboard Sounder | |
| Product dimensions (mm) | |
| Construction & finish | |
| IP Rating | |
| Notes |